General specifications | |
---|---|
Signal type | Analog input |
Supply | |
Connection | SL1: 1a(-), 1b(-); 2a(+), 2b(+) |
Rated voltage | 20.4 ... 30 V DC bus powered via Termination Board |
Rated current | 30 mA at 24 V, 20 mA output |
Power dissipation | 0.6 W at 24 V |
Input | |
Connection side | field side |
Connection | SL2: 5a(+), 7a(-): thermocouples type E, J, K, N, R, S, T 5a(+), 7b(-): thermocouple type B and mV input 5b(+), 7b(-): cold junction compensation (CJC) |
Thermocouples | type B, E, J, K, N, R, S, T (IEC584-1), type L (GOST) |
Measurement range | -10 ... 100 mV |
Span | 2.6 ... 100 mV |
Zero suppression | ± 500 % of span |
Line fault detection | sensor burnout 25 nA, upscale or downscale (selectable) |
Output | |
Connection side | control side |
Connection | SL1: 8a(+), 7a(-) |
Load | 0 ... 650 ? |
Output signal | 4 ... 20 mAИли отправьте нам запрос на1 % internal shunt) |
Ripple | 10 mVrms (at load 250 ?) |
Transfer characteristics | |
Accuracy | < ± 0.1 % of full-scale value (current output) |
Influence of temperature | < ± 0.01 %/K on zero and span |
Influence of load | < ± 0.1 % of full-scale value from 0 ... 650 ? |
Rise time/fall time | typ. 150 ms |
Linearity | < ± 0.1 % of full-scale value (terminal based mV input to mA output of thermocouples) |
Compensation error | ± 0.5 K ± 0.05 K deviation from reference of 20 °C (68 °F) |
Indicators/settings | |
Display elements | LED |
Control elements | DIP-switch potentiometer |
Configuration | via DIP switches via potentiometer |
Labeling | space for labeling at the front |
Directive conformity | |
Electromagnetic compatibility | |
Conformity | |
Electromagnetic compatibility | NE 21:2006 For further information see system description. |
Degree of protection | IEC 60529 |
Ambient conditions | |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications | |
Degree of protection | IP20 |
Mass | approx. 140 g |
Dimensions | 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch) |
Mounting | on Termination Board |
Data for application in connection with hazardous areas | |
EU-Type Examination Certificate | CESI 02 ATEX 086 |
Certificate | PF 11 CERT 2109 X |
Directive conformity | |
International approvals | |
CSA approval | |
IECEx approval | IECEx TUN 04.0012 |