Technical data | EPP3632-0001 |
---|
Technology | Condition Monitoring/IEPE |
Sensor types | IEPE |
Connection method | M8, 4-pin, screw type, shielded |
Number of inputs | 2 |
Signal voltage | IEPE constant current supply and recording of modulated AC voltage |
Sensor state monitoring | yes, through monitoring of the bias voltage |
Measuring range | default ±5 V up to 25 kHz, ±250 mV up to 10 Hz |
Input filter limit frequency | analog parameterisable 5th order low-pass filter up to 25 kHz, typically 0.05 Hz high-pass filter |
Measuring error | < ±0.5="" %="" (dc;="" relative="" to="" full="" scale=""> |
Resolution | 16 bit (incl. sign) |
Nominal voltage | 24 V DC (-15 %/+20 %) |
Conversion time | 20 μs (max. 50 ksamples/s) |
Supply current IEXCITE | typ. 2/4/8 mA (separately configurable for both channels) |
Sensor supply | from control voltage US |
Current consumption | typ. 120 mA |
Distributed clocks | yes |
Special features | automatic anti-aliasing function, wire breakage detection |
Bus interface | 2 x M8 socket, shielded, screw type, EtherCAT-P-coded |
Electrical isolation | 500 V |
Weight | approx. 165 g |
Operating/storage temperature | -25…+60 °C/-40…+85 °C |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos. | IP 65/66/67 (conforms to EN 60529)/variable |
Approvals/markings | CE, UL |